Smart Line Module in booksize compact format
 

Technical specifications for Booksize format

 

General technical specifications

Unless explicitly specified otherwise, the following technical specifications are valid for all components of the SINAMICS S120 booksize drive system.
 

Note:

When engineering the complete SINAMICS S120 drive, the system data of the associated Control Units, supplementary system components, DC link components and Sensor Modules must be taken into consideration.

Electrical specifications

Line voltage

380 ... 480 V 3 AC ±10 % (-15 % <1 min)

Line system configurations

Grounded TN/TT systems and non-grounded IT systems

Line frequency

47 ... 63 Hz

Electronics power supply

24 V DC -15 %/+20 %1), safety extra low-voltage (PELV/SELV)

Short-circuit current rating (SCCR)

(Short Circuit Current Rating)
according to UL 508C (up to 600 V)

1.1 ... 447 kW: 65 kA

Electromagnetic compatibility

According to EN 61800‑3

Second environment, Category C2/C3

For further information, see section Configuration notes

Overvoltage category

According to IEC/EN 61800‑5‑1

III

Mechanical specifications

Degree of protection

 

  • According to EN 60529

IP20

  • According to UL 508C/UL 61800‑5‑1

Open type

Protection class

 

  • Line circuits with protective conductor connection according to IEC 61800‑5‑1

I

  • Electronic circuits

Safety extra low-voltage PELV/SELV

Ambient conditions

 

Storage

Transport

Operation

In product packaging

In transport packaging

 

Climatic environmental conditions

Class 1K4
acc. to EN 60721‑3‑1
-25 ... +55 °C (-13 ... +131 °F)

Class 2K4
acc. to EN 60721‑3‑2
-40 ... +70 °C (-40 ...+158 °F)

Class 3K3 3)
acc. to EN 60721‑3‑3
For operation without derating4): 0 ... +40 °C (32 ...104 °F)
For operation with derating: >40 ... +55 °C (>104 ... 131 °F)

Relative humidity 5 ... 95 %

Environmental class/harmful chemical substances

Class 1C2
acc. to EN 60721‑3‑1

Class 2C2
acc. to EN 60721‑3‑2

Class 3C2
acc. to EN 60721‑3‑3

Organic/biological influences

Class 1B1
acc. to EN 60721‑3‑1

Class 2B1
acc. to EN 60721‑3‑2

Class 3B1
acc. to EN 60721‑3‑3

Pollution degree 2)

acc. to IEC/EN 61800‑5‑1

2

Installation altitude

 

  • Up to 1000 m (3281 ft) above sea level

Without derating

  • From 1000 m (3281 ft) up to 2000 m (6562 ft) )above sea level observe the derating characteristics
  • Reduction of the output current by 10 % per 1000 m (3281 ft) or
  • Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)
  • From 2000 m (6562 ft) up to 4000 m (13123 ft) above sea level observe the derating characteristics

 

  • Power components
  • Reduction of the output current by 10 % per 1000 m (3281 ft) or
  • Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)

and additionally:

  • Operation on line supply systems with grounded neutral point, or
  • Operation with an isolating transformer with secondary grounded neutral point
  • Control Units
  • Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)

Mechanical strength

 

Storage

Transport

Operation

In product packaging

In transport packaging

 

Vibratory load

Class 1M2
acc. to EN 60721‑3‑1

Class 2M3
acc. to EN 60721‑3‑2

Class 3M1
acc. to EN 60721‑3‑3
Test valuesacc. to EN 60068‑2‑6 :
10 oscillations per axis in the range: 10 ... 57 Hz constant deflection 0.075 mm
57 ... 150 Hz constant acceleration 9.81 m/s2(1 × g)

Shock load

Class 1M2
acc. to EN 60721‑3‑1

Class 2M3
acc. to EN 60721‑3‑2

Class 3M1
acc. to EN 60721‑3‑3
Test valuesacc. to EN 60068‑2‑27 :
3 shocks per axis in both directions
Peak acceleration 49 m/s2 (5 × g); duration 30 ms

Certificates

Declarations of conformity

CE (Low Voltage, EMC and M​achinery Directive)

Certificates of suitability

cULus

 

1) When using a motor holding brake, restricted voltage tolerances (24 V ±10 %) might need to be taken into account.
 

2) The components must be protected against conductive pollution, e.g. by installing them in a control cabinet with degree of protection IP54 according to IEC 60529 or NEMA 12. If conductive pollution can be excluded at the installation site, a lower degree of cabinet protection is permissible.
 

3) Better than 3K3 through increased ruggedness regarding the temperature range and humidity. Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing water and water jets are not permitted.

4) Also carefully observe the permissible temperatures for the Control Unit and operator panel.

 

Chi tiết về sản phẩm SINAMICS S120 built-in units > Booksize format > Active Line Modules in booksize format


Smart Line Modules are stall-protected, line-commutated infeed/regenerative feedback units (diode bridge for incoming supply; stall-protected, line-commutated regenerative feedback via IGBTs) with 100 % continuous regenerative feedback power. The regenerative capability of the modules can be deactivated by means of parameterization. Smart Line Modules are designed for connection to grounded TN/TT systems and non-grounded IT systems.

The DC link is pre-charged via integrated precharging resistors.

The associated line reactor is required for operating a Smart Line Module.

 

Design

The Smart Line Modules in booksize compact format feature the following connections and interfaces as standard:

- 1 power connection via screw-type terminals
- 1 connection for the 24 V DC electronics power supply via the 24 V terminal adapter included in the scope of supply
- 1 DC link connection via integrated DC link busbars
- 2 PE (protective earth) connections
- 3 DRIVE‑CLiQ sockets


The status of the Smart Line Modules is indicated via two multi-color LEDs.

The signal cable shield can be connected to the Line Module by means of a shield connection terminal, e.g. Weidmüller type KLBÜ 3‑8 SC.


The scope of supply of the Smart Line Modules includes:

- DRIVE‑CLiQ cable for connection to the adjacent Control Unit on the left for drive control, length 0.11 m (4.33 in)
- 2 blanking plugs for sealing unused DRIVE‑CLiQ sockets
- DRIVE‑CLiQ cable for connecting to the adjacent Motor Module, length 0.21 m (8.3 in)
- Jumper for connecting the 24 V DC busbar to the adjacent Motor Module
- 24 V terminal adapter (X24)
- Connector X21 for digital inputs/outputs
- 1 set of warning signs in 30 languages
- 1 heat conducting foil

 

Integration

The Smart Line Module receives its control information via DRIVE-CLiQ from:

- CU320‑2 Control Unit
 - SIMOTION D

Connection example of Smart Line Module in booksize compact format

 

Technical specifications

 

Smart Line Module in booksize compact format

6SL3430-6TE21-6AA1

Line voltage

(up to 2000 m (6562 ft) above sea level)

380 ... 480 V 3 AC ±10 % (in operation -15 % <1 min)

Line frequency

47 ... 63 Hz

SCCR (short-circuit current rating)

65 kA in conjunction with the recommended Class J fuse, or circuit breaker according to UL489 / CSA 22.2 No. 5-02

see recommended line-side components

Line power factor

at rated power

 

  • Fundamental (cos φ1)

>0.96

  • Total (λ)

0.65 ... 0.9

Overvoltage category

according to EN 60664‑1

Class III

DC link voltage, approx.

1.35 × line voltage 1)

Electronics power supply

24 V DC, -15 %/+20 %

Radio interference suppression

 

  • Standard

No radio interference suppression

  • With line filter

Category C2 to EN 61800‑3
Total cable length up to 350 m (1148 ft) (shielded)

Type of cooling

Internal air cooling (power units with increased air cooling by built-in fan)

Permissible ambient and coolant temperature (air)

during operation for line-side components, Line Modules and Motor Modules

0 ... 40 °C (32 ... 104 °F) without derating,
> 40 ... 55 °C (104 ... 131 °F), see derating characteristics

Installation altitude

Up to 1000 m (3281 ft) above sea level without derating,
> 1000 ... 4000 m (3281 ... 13124 ft) above sea level, see derating characteristics

Declarations of conformity

CE (Low Voltage and EMC Directives)

Certificate of suitability

UL recognized

 

1) The DC link voltage is regulated to the mean value of the rectified line voltage. For further information, see section Configuration notes.

 

Line voltage 380 ... 480 V 3 AC

Smart Line Module in booksize compact format

Internal air cooling

6SL3430-6TE21-6AA1

Infeed/regenerative feedback power

 

  • Rated power Prated
 

 

  • at 380 V 3 AC

16 kW

  • at 460 V 3 AC 2)

(18 hp)

  • For S6 duty (40 %) PS6

21 kW

  • Pmax

35 kW

DC link current

 

  • At 600 V DC

27 A

  • For S6 duty (40 %)

35 A

  • Maximum

59 A

Input current

 

  • Rated current at 380 V 3 AC

29 A

  • For S6 duty (40 %)

35 A

  • Maximum

57.5 A

Current requirement

24 V DC electronics power supply, max.

1.1 A

Current carrying capacity

 

  • 24 V DC busbars

20 A

  • DC link busbars

100 A

DC link capacitance

 

  • Smart Line Module

705 μF

  • Drive line-up, max.

6000 μF

Power loss 1)

0.19 kW

Cooling air requirement

0.016 m3/s (0.57 ft3/s)

Sound pressure level

LpA (1 m)

<60 dB

Line connection

U1, V1, W1

Screw-type terminals (X1)

  • Conductor cross-section, max.

2.5 ... 10 mm2

Shield connection

Cable shield connection plate integrated into the connector

PE connection

M5 screw

Cable length, max.

(total of all motor cables and DC link)

 

  • Shielded

630 m (2067 ft)

  • Unshielded

850 m (2788 ft)

Degree of protection

IP20

Dimensions

 

  • Width

100 mm (3.94 in)

  • Height

270 mm (10.6 in)

  • Depth

226 mm (8.90 in)

Weight, approx.

5.3 kg (12 lb)

 

1) Power loss of Smart Line Module at rated output including losses of 24 V DC electronics power supply.

2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be dimensioned accordingly.

 

Characteristic curves

Overload capability

Duty cycle with previous load

S6 duty cycle with previous load

S6 duty cycle with previous load

Derating characteristics

Output power as a function of ambient temperature

Installation altitude

- >1000 ... 4000 m (3281 ... 13124 ft) above sea level
  + Reduction of the output current by 10 % per 1000 m (3281 ft), or
  + Reduction of the ambient temperature by 5 °C (9 °F) per 1000 m (3281 ft)
  • >2000 ... 4000 m (6562 ... 13124 ft) above sea level
  + Operation on line supply systems with grounded neutral point, or
  + Operation with an isolating transformer with secondary grounded neutral point
 